Products

- Energz High Joiner

Air-cooled in-room precision air conditioner KHJA (7.5-20kW)

Brief

The Energz High Joiner (7.5KW -20KW) air cooled series provides professional cooling solutions for base stations and small to medium-sized machine rooms, etc. As an important part of a machine room, it is designed to match the environment in which the equipment is located, configures with a constant temperature and humidity function, and features high airflow rate, low enthalpy difference and a high sensible heat ratio, soas to realize maximum reliability, long service life, and high energy efficiency and thus ensure the all-weather and energy- efficient operation of units.

Application

  •  Base stations
  •  Small and medium-sized machine rooms
  •  Small and medium-sized storage rooms and laboratories
  •  Small data room

Customer Value

 Highly efficient – saving money

  •  High energy efficiency ratio, high sensible heat ratio, efficient refrigeration, and high energy efficiency
  •  High quality condenser, compact design, light weight, and convenient for installation, operation and maintenance
  • An EC fan with high airflow rate, R410A environment-friendly refrigerant as a standard configuration, advanced noise reduction, and energy efficiency
  •  Self-contained quick couplings requiring no welding, facilitating flexible installation, and efficient operation and maintenance
  • Compact design, small footprint, and optimized structure, greatly saving machine room space and reducing ownership costs for customers
  • Low power consumption wet film humidifier, energy saving, wide application range.

Highly intelligent – time-saving

  • An electrode humidifier is used to realize high humidification efficiency and a wide application range
  • Capable of on-site monitoring and remote monitoring, ensuring efficient operation and maintenance
  • Standard RS485 interface, local and remote monitoring
  • A complete set of self-check, alarm and protection functions
  • Intelligent control system, centralized control over multiple machines and featuring timing patrol and automatic failsafe
  • Ultra-wide power grid adaptabilty, featuring phase sequence protection, self-starting when power is restored, and delayed start.
  •  Chinese LCD screen, multi-level password permission, self-check diagnosis function for management  experts in the air conditioning field, and easy operation and maintenance
  • The indoor unit adopts 100% front maintenance and a pull-out module design, greatly improving operation and maintenance efficiency.

Highly  reliable – worry-free

  • Efficient and refiable compressor used to ensure the reliabilty of system operation
  • 24 hours x 365 days full-time operation, designed with a ten-year lifespan, low operation and maintenance costs.
  • Ultra-wide operating temperature range (outdoor- -35°C to 45°C); operation under ultra-low temperatures is possible for outdoor installations

Technical Specifications

K  A B 8 AU K J A- PBAU KHJ A- B12A U KH JA-  12 AU K JA- B 20 K  J A P 20 A U
Main power 380V/3PH/50Hz
Air supply mode Upward
Cooling capacity (kW) 7.5 7.5 12.5 115 20.0 20.0
Realistic capacity (kW) 6.8 6.8 11.3 11.3 18.0 18.0
Circulating air volume (m’/h) 2300 2300 3600 3600 5400 5400
Heating capacity (kW) / 3 3 3
Numidifying capacity (kg/h) 1.S 1.S 2
Width (mm) 550 550 650 650 800 800
Depth (mm) 4S0 4S0 450 450 650 650
Height (mm) 1800 1800 1800 1800 1800 1800
Max. operating current (A)

Weight (kg)

8.4

112

13.0

î18

11.9

132

16.5

138

21.8

168

26.3

174

 

hH N R 8 H N R 8 HN  12 K N 12 HN 0 K  N  20
Main power 220V/1PH/50Hz
Width (mm) 728 728 728 1080 1080
Depth (mm) 405 405 405 405 405 405
Height (mm) 762 762 1372 1372 1372 1372
Weight (kg) 34 34 53 53 85 85

 Notes:

  • Unit return air condtion: 1. Indoor return air: 24°C/50%RH, outdoor: 35°C. 2. Indoor return air: 37°C/26%RH, outdoor: 35°C.
  • The unit comes standard with R410A refrigerant, EC fan, and electronic expansion valve
  • Air supply method: The standard air supply method is a sinking fan air supply, and optional wind cap upward air supply and semi-sinking fan air supply are available.
  • The size and weight of the outdoor unit in the table above are parameters for a single outdoor unit. The 60kW/80kW/100kW is a dual-system model, and each indoor unit is configured with two outdoor units The height of the outdoor unit does not include support feet .
  • For details on the centralized outdoor unit with an integrated freon pump, please see the outdoor unit promotion page.